Bryant Furnace Error Codes

LED CODE STATUS
CONTINUOUS OFF Check for 115 VAC at L1 &L2, & 24VAC at SEC-1 & SEC-2
CONTINUOS ON CONTROL HAS 24VAC POWER.
RAPID FLASHING LINE VOLTAGE (115VAC) POLARITY REVERSED OR FURNACE NOT GROUNDED

Bryant Furnace Error Code Chart

Book your Free Inspection for a Quote!

Please click the button below, one of our advisers will give you a call.

BRYANT ERROR CODE 11

NO PREVIOUS CODE - STORED STATUS CODES ARE ERASED AUTOMATICALLY AFTER 72 HOURS OR AS SEPCIFIED ABOVE

BRYANT ERROR CODE 12

BLOWER ON AFTER POWER UP (115VAC or 24VAC)

Blower runs for 90 seconds, if unit is powered up during a call for heat (R-w/w1 closed) or (R-w/w1) opens during blower on delay period.

BRYANT ERROR CODE 13

LIMIT CIRCUIT LOCKOUT

Lockout occurs if a limit or flame rollout switch is open longer than 3 minutes or 10 successive limit tips occurred during high-heat.

BRYANT ERROR CODE 14

IGNITION LOCKOUT

Control will auto-reset after 3 hours.

BRYANT ERROR CODE 21

GAS HEATING LOCKOUT

Control will NOT auto reset after 3 hours.

BRYANT ERROR CODE 22

ABNORMAL FLAME-PROVING SIGNAL

Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared.
Check for
Leaky Gas Valve
Stuck open gas valve

BRYANT ERROR CODE 23

PRESSURE SWITCH DID NOT OPEN

Check for: –

Obstructed pressure tubing -Pressure switch stuck closed

BRYANT ERROR CODE 24

SECONDARY BOLTAGE FUSE IS OPEN

Check for: –

  • Short circuit in secondary voltage(24VAC) wiring.

BRYANT ERROR CODE 25

MODEL SELECTION OR SETUP ERROR

Eiher indicates the model plug (PL4) is missing or incorrect or setup switch “SW1-1” or “SW1=6” is positioned improperly. If code flashes only 4 times on power-up control is defaulting to model selection stored in memory.
Check the following:

  • Thermostat call with “SW-1” ON
  • Thermostat call with “SW-6” ON
  • “SW1-1” and “SW1-6” both ON together
  • Two different furnace models twinned
  • Wiring diagram for model plug number and resistance values if code flashes continuously

BRYANT ERROR CODE 31

HIGH-HEAT PRESSURE SWITCH OR HPSR RELAY DID NOT CLOSE OR REOPENED

Indicates the high heat pressure switch input failed to close on a call for high-heat, or opened during high-heat. HPSR relay may be defective. Refer to status code#32

BRYANT ERROR CODE 32

LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED

Indicates the low-heat pressure switch input failed to close on a call fcr low-heat, or opened during low-heat. If opens during 5 minutes alter ignition the next heating cycle will be restricted to high-heat.

Check for

  •  Proper vent sizing
  • Improper pressure switch wiring – Restricted combustion air supply
  • Plugged condensate drain – Excessive wind              -Low inlet gas pressure (if LGPS used)
  • Disconnected or obstructed pressure tubing • Water in vent piping. possible sagging pipe
  • Failed or ‘Out-of-Calibration’ pressure switches

BRYANT ERROR CODE 33

LIMIT CIRCUIT FAULT

Indicates a limit or flame rollout, is open or the furnace is operating in high-heat only mode due to 2 successive low heat limit trips. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off.
Flame rollout switch requires manual reset.
Check for:

  • Improper limit switch or no limit gasket
  • Defective switch or connections
  • Improper low or high-heat gas input adjustment – Loose blower wheel
  • Stuck high-heat solenoid in gas valve

BRYANT ERROR CODE 34

IGNITION PROVING FAULT

– Control will try three more times before lockout 414 occurs. If flame signal lost during blower on-delay period: blower will come on for the selected blower off-delay. Check for:

  • Oxide buildup on flame sensor (clean with tune steel wool) Manual valve shut-0g -Control ground continuity
  • Proper flame sense microamps (.5 microamps D.C. min.. 4.0 – 6.0 nominal) Gas valve defective turned ‘OFF’
  • Low inlet gas pressure – Inadequate flame carryover or rough ignition – Defective Hol Surface Ignitor
  • Flame sensor must not be grounded
  • Green/yellow wire MUST be connected to furnace sheet metal

BRYANT ERROR CODE 43

LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED

Check for:

  • Plugged condensate drain – low inlet gas pressure (if LGPS used)            – Improper pressure switch wiring
  • Water in vent piping, possibly sagging pipe – Stuck open low-heat pressure switch
  • Disconnected or obstructed pressure tubing

BRYANT ERROR CODE 45

CONTROL CIRCUITRY LOCKOUT
  • Auto-reset after 1 hour lockout due to;
  • Gas valve relay contact stuck open – Flame sense circuit failure Software check error
    Reset power to clear lockout. Replace control if status code repeals.